7#Secondary Spray Pump 10kv Substation 3#堆浸场7#次级喷淋泵站10KV配电室 Installation position:1# Incoming Line 1.设备参数Equipment parameter: 型号Model 工作电压Work voltage 相数 Phases ZR-YJV-8.7/10KV 8.7/10KV 3 高压电缆试验记录 HV Cable Test Records 2.绝缘电阻测试:Insulation resistance test: 检测环境条件Check ambient condition:温度temperature 34 ℃ 湿度HR 60 % A对B.C地 A to B, C and PE (GΩ) >100 B对A.C地 B to A, C and PE (GΩ) >100 C对A.B.地 C to A, B and PE (GΩ) >100 耐压前 before withstand voltage test 耐压后 >100 >100 >100 after withstand voltage test 3.直流耐压测试:DC withstand voltage test 试验电压 test voltage(KV) A对B.C地 A to B, C and PE(μA) B对A.C地 B to A, C and PE(μA) C对A.B.地 C to A, B and PE(μA) 10 0 0 0 20 1 0 0 30 3 2 2 34.8 4 3 4 4.相序核对Check Phases 相别Phases Phases A Phases B Phases C 5.试验设备:test equipment 名称equipment 型号type 编号NO. 精度precision 两端色标check colour 黄Yellow 绿Green 红Red 结果check result 黄Yellow 绿Green 红Red 绝缘电阻测试仪 Insulation Resistance Tester 万用表multimeter 直流高压发生器 High voltage power supply 3125 179 ZGS-300/3 \\ 1502003 \\ \\ \\ C3051076 6.结论Conclusion: 合格OK personnel 业主人员 Proprietor 总包人员 General contractor 调试人员 Tester Blank
signature date 7#Secondary Spray Pump 10kv Substation 3#堆浸场7#次级喷淋泵站10KV配电室 Installation position:2# Incoming Line 1.设备参数Equipment parameter: 型号Model 工作电压Work voltage 相数 Phases ZR-YJV-8.7/10KV 8.7/10KV 3 高压电缆试验记录 HV cable test records 2.绝缘电阻测试:Insulation resistance test: 检测环境条件Check ambient condition:温度temperature 34 ℃ 湿度HR 60 % A对B.C地 A to B, C and PE (GΩ) >100 B对A.C地 B to A, C and PE (GΩ) >100 C对A.B.地 C to A, B and PE (GΩ) 87 耐压前 before withstand voltage test 耐压后 >100 >100 >100 after withstand voltage test 3.直流耐压测试:DC withstand voltage test 试验电压 test voltage(KV) A对B.C地 A to B, C and PE(μA) B对A.C地 B to A, C and PE(μA) C对A.B.地 C to A, B and PE(μA) 10 0 0 0 20 0 1 0 30 4 5 3 34.8 7 8 6 4.相序核对check Phases 相别Phases Phases A Phases B Phases C 5.试验设备:test equipment 名称equipment 型号type 编号NO. 精度precision 两端色标check colour 黄Yellow 绿Green 红Red 结果check result 黄Yellow 绿Green 红Red 绝缘电阻测试仪 Insulation Resistance Tester 万用表multimeter 直流高压发生器 High voltage power supply 3125 179 ZGS-300/3 \\ 1502003 \\ \\ \\ C3051076 6.结论conclusion:合格 OK personnel 业主人员 Proprietor 总包人员 General contractor 调试人员 Tester Blank
signature date 7#Secondary Spray Pump 10kv Substation 3#堆浸场7#次级喷淋泵站10KV配电室 Installation position:Transformer 1.设备参数Equipment parameter: 型号Model 工作电压Work voltage 相数 Phases ZR-YJV-8.7/10KV 8.7/10KV 3 高压电缆试验记录 HV cable test records 2.绝缘电阻测试:Insulation resistance test: 检测环境条件Check ambient condition:温度temperature 34 ℃ 湿度HR 60 % A对B.C地 A to B, C and PE (GΩ) >100 B对A.C地 B to A, C and PE (GΩ) >100 C对A.B.地 C to A, B and PE (GΩ) 87 耐压前 before withstand voltage test 耐压后 >100 >100 >100 after withstand voltage test 3.直流耐压测试:DC withstand voltage test 试验电压 test voltage(KV) A对B.C地 A to B, C and PE(μA) B对A.C地 B to A, C and PE(μA) C对A.B.地 C to A, B and PE(μA) 10 0 0 0 20 0 1 0 30 2 5 2 34.8 4 6 5 4.相序核对check Phases 相别Phases Phases A Phases B Phases C 5.试验设备:test equipment 名称equipment 型号type 编号NO. 精度precision 两端色标check colour 黄Yellow 绿Green 红Red 结果check result 黄Yellow 绿Green 红Red 绝缘电阻测试仪 Insulation Resistance Tester 万用表multimeter 直流高压发生器 High voltage power supply 3125 179 ZGS-300/3 \\ 1502003 \\ \\ \\ C3051076 6.结论conclusion: 合格OK personnel 业主人员 Proprietor 总包人员 General contractor 调试人员 Tester Blank
signature date